The review of these plans is to ensure the proper design and calculations are provided for compliance, with the below listed code, prior to the installation of the fire alarm and smoke detection system.

No. Fire Code Compliance Item
A-000Applicable Codes:
A-002Provide floor plans to include room designations and room dimensions NFPA 72; Chap. 7; Sect 7.4.5; 2019 Ed.
A-003Provide a sheet that identifies the matrix of operations for all systems and devices, with any design assumptions. NFPA 72; Chap. 7; Sect. 7.2.1(4); 2019 Ed.
A-004Provide point to point wiring diagrams including end of line resistors. NFPA 72; Chap. 7; Sect. 7.4.8; 2019 Ed.
A-006Provide appliance / device / equipment spec sheets. NFPA 72; Chap. 7; Sect. 7.2.1(5); 2019 Ed.
A-008Provide a copy of low voltage license. NFPA 72; Chap. 10; sect. 10.5.2; 2019 Ed.
A-010Is building equipped with an automatic sprinkler system? Authority Having Jurisdiction.
A-012Provide mounting heights of pull stations (42-54 inches above finished floor). Georgia Accessibility Code; Chap. 3; Sect 308; 2010 Ed.
A-014Provide mounting heights of strobes wall mount (80 inches above finished floor). Ceiling mounted strobe maximum of 30 feet above finished floor. NFPA 72; Chap. 18; Sect. 18.5.5.1, 18.5.5.2 and 18.5.5.4.6; 2019 Ed.
A-016Provide automatic sprinkler riser details if more than (1) riser is installed. Authority Having Jurisdiction.
A-018Provide symbols for devices used in fire alarm and identify candela size. NFPA 72; Chap. 7; Sect. 7.2.3; 2019 Ed.
A-020Provide class of system. NFPA 72; Chap. 12; Sect. 12.3; 2019 Ed.
A-022Provide secondary power supply. NFPA 72; Chap. 10; Sect. 10.6.7; 2019 Ed.
A-024Provide plenum rated wire above ceiling. NFPA 72; Chap. 7; Sect 7.4.5 (12).
A-026Provide Non-plenum rated wire. NFPA 72; Chap. 7; Sect. 7.4.5 (12).
A-028Provide annunciator panel location in lobby / reception area or at a constantly attended location. NFPA 72; Chap. 10; Sect. 10.18.3; 2019 Ed.
A-030Verify Fire Alarm control panel location. Make sure it is placed in a UL approved protected enclosure or placed in an environmentally protected area. Must meet the temperature ranges of 32 to 120 degrees Fahrenheit. NFPA 72; Chap. 10; Sect. 10.18.3.2; 2019 Ed.
A-032Identify all Fire Alarm zones at annunciator. NFPA 72; Chap. 10; Sect. 10.18.4; 2013 Ed.
A-034Hood system shall be wired to Fire Alarm. NFPA 17A; Chap. 5; Sect. 5.3.1. 2019 Ed.
A-036Provide detector in Elevator lobby. NFPA 101; Chap. 9; Sect. 9.6.3.2.2; 2018 Ed.
A-040Verify if HVAC duct detectors show trouble and shut unit down. NFPA 72; Chap. 17; Sect. 17.5.3.1.4(2); 2019 Ed.
A-042Provide a smoke or heat detector for Automatic door release. NFPA 72; Chap. 17; Sect. 17.7.5.6; 2019 Ed.
A-044Provide supervision for Dry pipe sprinkler systems. NFPA 72; Chap. 17; Sect 17.16.2.2.2; 2019 Ed.
A-046Provide supervision for Control valves. NFPA 72; Chap. 17; Sect. 17.16.1; 2019 Ed.
A-048Provide supervision for Pressure sources. NFPA 72; Chap. 17; Sect 17.16.2.2.1; 2013 Ed.
A-050Provide supervision for Water level. NFPA 72; Chap. 17; Sect. 17.16.3; 2019 Ed.
A-052Provide supervision for Water temperature. NFPA 72; Chap. 17; Sect 17.16.4; 2019 Ed.
A-054Provide supervision for Fire pump. NFPA 72; Chap. 23; Sect. 23.8.5.9.2; 2019 Ed.
A-056Provide supervision for automatic phone dialer for offsite monitoring. NFPA 72; Chap. 26; Sect. 26.5.1.4; 2019 Ed.
A-058Provide voice evacuation in places of assembly with an occupant load of 300 persons or more. NFPA 101; Chap. 12; Sect 12.3.4.3.6; 2018 Ed.
A-060Provide voice evacuation with alternate power supply. NFPA 101; Chap. 9; Sect. 9.6.3.9.2(2); 2018 Ed.
A-062Verify if speakers override sound system. NFPA 101; Chap. 9; Sect. 9.6.3.9.2(3); 2012 Ed.
A-064    Provide voice evacuation with automatic operation. NFPA 101; Chap. 9; Sect. 9.6.3.9; 2018 Ed.
A-066Provide voice evacuation with microphone and manual override. NFPA 101; Chap. 9; Sect. 9.6.3.9.2(4); 2018 Ed.
A-068Provide a fire alarm and/or smoke detection system complying with the requirements of the occupancy chapter of the NFPA 101 Life Safety Code, 20182 Ed.
A-070 Provide mini horn in apartment dwelling units to achieve minimum db. Authority having Jurisdiction.