This review is to ensure that the proposed commercial kitchen hood over the cooking appliances (ranges, deep fryers, woks, etc.) complies with the above listed standard for the proper ventilation of grease laden vapors to the outside and for the fire safety of the structure in which it is to be installed.

No.Fire Code Compliance Item
H-000Applicable Codes: This code reference shall be placed on the cover sheet of your drawings. NFPA 96; 2017 Ed.
H-002Maintain 40 inches clear above the roof with the exhaust flow pointed up & away from the roof surface
H-004Duct access panels shall be identified by a sign per NFPA 96, 4-1.6.; 2017 Ed.
H-006Duct access panels shall be provided per NFPA 96, 4-3.; 2017 Ed.
H-008Provide verification that the proposed exhaust fan is approved for this type of installation.
H-010Back shelf hoods shall provide 300 cfm of air flow per linear feet of cooking surface.
H-012Canopy hood open on 3 sides shall provide 100 cfm of air flow per square feet of hood.
H-014Canopy hoods open all sides shall provide 150 cfm of air flow per square feet of hood.
H-016Provide verification that the product complies with the requirements of the clearance reduction table.
H-018Maintain 18 inches from combustible materials to Hood & Duct.
H-020A Drip tray & Cup shall be installed below the bottom edge of the filters.
H-022Duct construction shall comply with NFPA 96, 4-5.2.; 2017 Ed.
H-024Duct Clearances shall be maintained per NFPA 96, 1-3.2.1.; 2017 Ed.
H-026Exhaust Fan clearances shall be maintained per NFPA 96, 1-3.2.1.; 2017 Ed.
H-028Exterior duct installation shall comply with NFPA 96, 4-6.; 2017 Ed.
H-030Maintain 10 ft. clearance from adjacent Buildings, Property lines & Air intakes.
H-032Grease removal devices shall comply with NAPA 96, 3-1 & 3-2.; 2017 Ed.
H-034Grease removal device clearances shall be maintained per NFPA 96, 1-3.2.1; 2017 Ed.
H-036Hood Clearances shall be maintained per NFPA 96, 1-3.2.1; 2017 Ed.
H-040The Hood shall be a maximum of 7 feet Above finished floor to the bottom edge of the hood.
H-042Filters shall be installed at 45 degree angles.
H-044Interior duct installation shall comply with NFPA 96, 4-7.; 2017 Ed.
H-046Ducts shall lead directly to the exterior of the building. NFPA 96, 4-1.2; 2017 Ed.
H-048Maintain 3 inches from limited combustible materials to Hood & Duct.
H-050Provide verification from the testing agency as to the listing they have given this product.
H-052Make up air shall be a minimum of 80% of exhaust air.
H-054Ducts shall form no dips and/or traps per NFPA 96, 4-1.4.; 2017 Ed.
H-056Ducts shall not connect to any other ventilation or exhaust system NFPA 96, 4-1.3; 2017 Ed.
H-058Maintain 0 inches clearance from non-combustible materials to Hood & Duct.
H-060Ducts shall not pass through fire walls or fire partitions. NFPA 96, 4-1.1; 2017 Ed.
H-062Rooftop terminations shall comply with NFPA 96, 4-8.2.; 2017 Ed.
H-064Wall terminations shall comply with NFPA 96, 4-8.3.; 2017 Ed.